HEATER & AIR CONDITIONER
REFRIGERANT
REFRIGERANT
ON–VEHICLE INSPECTION
550IQ–01
1.
INSPECT REFRIGERANT PRESSURE WITH MAN-
IFOLD GAUGE SET
(a)
This is a method in witch the trouble is located by using
a manifold gauge set. Read the manifold gauge pressure
when the these conditions are established.
Test conditions:
Temperature at the air inlet with the switch set
at RECIRC is 30 – 35 ° C (86 – 95 ° F)
Engine running at 1500 rpm
Blower speed control switch at ”HI” position
Temperature control dial at ”COOL” position
A/C switch ON
Fully open doors
(1) Normally functioning refrigeration system.
Gauge reading:
Low pressure side:
0.15 – 0.25 MPa (1.5 – 2.5 kgf/cm 2 )
High pressure side:
1.37 – 1.57 MPa (14 – 16 kgf/cm 2)
E50573
(2)
Moisture present in refrigeration system.
Condition : Periodically cools and then fails to cool
I22117
Symptom
Probable cause
Diagnosis
Remedy
Moisture in refrigerating system
freezes at expansion valve orifice
causing a temporary stop of cycle,
however, when it melts, normal
state is restored.
Drier in oversaturected state
(1) Replace condenser
(2) Remove moisture in cycle by
repeatedly evacuating air
(3) Supply proper amount of new
refrigerant
During operation, pressure on low
pressure side sometimes become
a vacuum and sometime normal
Moisture in refrigerating system
freezes at expansion valve orifice
and blocks circulation of refriger-
ant
2004 COROLLA (RM1037U)
Author:
Date:
1576
751624926.047.png 751624926.052.png 751624926.053.png 751624926.054.png 751624926.001.png 751624926.002.png 751624926.003.png 751624926.004.png
 
55–7
HEATER & AIR CONDITIONER
REFRIGERANT
(3)
Insufficient cooling
Condition: Cooling system does not function eftectively.
I22118
Symptom
Probable cause
Diagnosis
Corrective Actions
(1) Check for gas leakage and re-
pair if necessary
(2) Supply proper amount of new
refrigerant
(3) If indicated pressure value is
close to a 0 when connected to
gauge, create the vacuum after in-
specting and repairing location of
leak
Pressure low on both low and
high pressure sides
Insufficient cooling performance
Gas leakage in refrigeration sys-
tem
Insufficient refrigerant
Refrigerant leaking
(4)
Poor circulation of refrigerant
Condition: Cooling system close not function effectively.
I22119
Symptom
Probable cause
Diagnosis
Corrective Action
Pressure low on both low and
high pressure sides
Refrigerant flow obstructed by dirt
in receiver
Receiver clogged
Replace condenser
Frost on pipe from condenser to
unit
2004 COROLLA (RM1037U)
Author:
Date:
1577
751624926.005.png 751624926.006.png 751624926.007.png 751624926.008.png 751624926.009.png 751624926.010.png 751624926.011.png 751624926.012.png 751624926.013.png 751624926.014.png 751624926.015.png
 
55–8
HEATER & AIR CONDITIONER
REFRIGERANT
(5)
Refrigerant does not circulate
Condition: Cooling system does not function. (Sometimes it way function)
I22120
Symptom
Probable cause
Diagnosis
Corrective Actions
(1) Check expansion valve
(2) Clean out dirt in expansion
valve by air blowing
(3) Replace condenser
(4) Evaporate air and supply prop-
er amount of new refrigerant.
(5) For gas leakage from expan-
sion valve, replace expansion
valve
Vacuum indicated on low pres-
sure side, very low pressure indi-
cated on high pressure side
Frost or dew seen on piping be-
fore and after receiver/ drier or ex-
pansion valve
Refrigerant flow obstructed by
moisture or dirt in refrigerating sys-
tem
Refrigerant flow obstructed by
gas leaked from expansion valve
Refrigerant does not circulate
(6)
Refrigerant overcharged or insufficient cooling of
condenser
Condition: Cooling system does not function dftectively.
I22121
Symptom
Probable cause
Diagnosis
Remedy
(1) Clean condenser
(2) Check cooling fan with cooling
fan motor operation
(3) If (1) and (2) are in normal
state, check amount of refrigerant
and supply proper amount of re-
frigerant
Excessive refrigerant in
cycle
Unable to develop sufficient per-
formance due to excessive use of
refrigerating system
"
too much refrigerant sup-
Pressure too high on both low
and high pressure sides
plied
Condenser cooling
insufficient
condenser fins
clogged at cooling fan
"
Insufficient cooling of condenser
2004 COROLLA (RM1037U)
Author:
Date:
1578
751624926.016.png 751624926.017.png 751624926.018.png 751624926.019.png 751624926.020.png 751624926.021.png 751624926.022.png 751624926.023.png 751624926.024.png 751624926.025.png 751624926.026.png 751624926.027.png 751624926.028.png
 
55–9
HEATER & AIR CONDITIONER
REFRIGERANT
(7)
Air present in refrigeration system
Condition: Cooling system does not function.
NOTE : These gauge indica-
tions are shown when the
refrigerating system has
been opens and the refriger-
ant charged without vacuum
purging.
I22122
Symptom
Probable cause
Diagnosis
Corrective Actions
(1) Check compressor oil to see if
it is see if it is dirty or insufficient
(2) Evacuate air and supply new
refrigerant
Pressure too high on both low
and high pressure sides
The low pressure piping too hot
to the touch
Air present in refrigerating sys-
tem
Insufficient vacuum purging
Air entered in refrigerating system
(8)
Expansion valve improperly
Condition: Refrigerant functions insufficient.
I22123
Symptom
Probable cause
Diagnosis
Corrective Actions
Pressure too high on both low
and high pressure sides
Frost or large amount of dew on
piping on low pressure side
Excessive refrigerant in low
pressure piping
Expansion valve opened too
wide
Trouble in expansion valve
Check expansion valve
2004 COROLLA (RM1037U)
Author:
Date:
1579
751624926.029.png 751624926.030.png 751624926.031.png 751624926.032.png 751624926.033.png 751624926.034.png 751624926.035.png 751624926.036.png 751624926.037.png 751624926.038.png 751624926.039.png
 
55–10
HEATER & AIR CONDITIONER
REFRIGERANT
(9)
Defective compression compressor
Condition : Refrigerant is not effective.
I22124
Symptom
Probable cause
Diagnosis
Corrective Actions
Pressure too high on low high
pressure sides
Pressure too low to on high pres-
sure side
Compression failure
Internal leak in compressor
Leakage from valve damaged or
broken sliding parts
Repair or replace compressor
Gauge readings (Reference)
Pressure on low pressure side
MPa (kgf/cm 2 )
0.5 (5.0)
Blower HI Zone
0.4 (4.0)
1.06 (10.9)
0.3 (3.0)
0.27 (2.85)
1.2 (12.3)
0.22 (2.25)
0.2 (2.1)
Blower LO Zone
0.2 (2.0)
1.25 (12.8)
0.14 (1.5)
1.32 (13.5)
Pressure on HI
pressure side
0.5 (5.0)
1.0 (10.0)
1.5 (15.0)
2.0 (20.0)
MPa (kgf/cm 2 )
I30081
2004 COROLLA (RM1037U)
Author:
Date:
1580