IEC 507-2 article.pdf

(318 KB) Pobierz
Investigations on rain fog pollution test - High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
4.111.S25
INVESTIGATIONS ON RAIN FOG POLLUTION TEST
D.Devendranath Pradeep M.Nirgude G.V.Rao RSShivakumara Aradhya
A.P. Sudheer* N.S.Mohan Rao
Channakeshava
UHV Research Laboratory
Central Power Research Institute
P.B.No.9, Uppal
Hyderabad, India - 500 039
*Dept. of Electrical Engg.
JNTU, Kakinada
Andhra Pradesh
India
Abstract
flashovers are more predominant since the flashover
occurs at the operating voltages or even at lower
values of system voltages. Thus, overcoming an
outage caused by pollution has become a crucial
thing in the power system. There are various factors
which signify the importance of the pollution
problem. First of all, the fast industrialization and
secondly the increase in the number of the thermal
power stations to meet the load requirement. The
industrial users are now demanding a higher quality
of electrical power supply. Besides, the pollution
phenomena is more severe with the increase in the
overhead transmission system voltages.
In the solid layer test method it is mentioned
that a warm or cold water may be used, instead of
steam for wetting the pollution layer. So an attempt
is made to perform the solid layer test with the
wetting action obtained from tap water, called the
Rain Fog test. An important aspect of this method is
that the existing spraying system of salt fog method
is used for the development. This will simulate the
actual conditions of the pollution layer wetted with
slight rain or drizzle or mist.
In the Rain Fog method, the insulator is
coated with a pollution whose layer conductivity
simulates the site condition and tap water fog is
applied to the insulator to simulate the actual rain,
dew or drizzle. The withstand capability of the
insulator string is tested as specified in IEC -
507,199 1. To standardize the Rain Fog test facility,
two tests are conducted viz. wetting action test (layer
conductance test) and reference test on nine disc
insulator string. These two tests are identical to the
tests necessary to standardize the solid layer test
facility as specified in IEC - 507. Rain fog test is a
combination of salt fog test as well as solid layer test
facility .
In the standards it is mentioned that warm
water or cold water may be used instead of steam for
wetting the pollution layer. So an attempt is made to
perform the solid layer test with wetting action
obtained from tap water, called the Rain Fog test.
This will simulate the actual conditions of the
pollution layer wetted with slight rain or drizzle or
mist. The power consumed in doing the test is less
when compared with the solid layer test as the time
taken for the saturation of wetting action curve is
less. As per IEC 507, for conducting solid layer test,
ambient temperature in the chamber at the start of the
test should not be less than 5
and test object should be in thermal equilibrium with
the ambient. But in tropical countries like India the
ambient temperature is more than 30 ' in sunmer. In
this case rain fog test is more helpful.
In the Rain Fog method two types of tests
are conducted :
nor grater than 30
1.0 Introduction
The increase in demand & losses lead power
system engineers to go for higher system voltages.
The increase in the system voltages have created a
number of problems such as the overvoltages
generated in the system due to nature, switching,
system faults, etc. These over voltages and faults
cause an outage in the part of the system or in the
whole system. So the overhead transmission lines are
designed based on the lightning overvoltages,
switching over voltages. However, pollution caused
High Voltage Engineering Symposium, 22-27 August 1999
Conference Publication No. 467, 0 IEE, 1999
1. Layer Conductance test ( wetting rate test)
2. Reference test
Authorized licensed use limited to: Biblioteka Glowna i OINT. Downloaded on March 08,2010 at 03:17:10 EST from IEEE Xplore. Restrictions apply.
255208996.001.png
4.112.S25
1.1 Layer Conductance Test
2.1 Layer Conductance Test:
In this method, the cleaned test specimen is
coated with the pollutant of required salinity by
dipping in the slurry and Rain fog is sprayed on
specimen. The voltage applied depends on the
creepage length of the total string. IEC-507 standard
specifies a voltage of > 700 Vrms per meter of the
overall creepage distance and measuring the current
flowing through the wet layer. The layer
conductance measurement is repeated on the
insulator during its wetting, with the aim of
detemiining the maximum value reached. The layer
conductivity is calculated by multiplying the layer
conductance measured on the unenergised insulator
by form factor. A graph is drawn between the time
and per unit leakage current. The curve is compared
with the standard curve given in IEC-507 standard.
The test duration is 90 min to 120 min. The test is
repeated several times for checking repeatability of
the values.
Two IEEE standard disc insulators are used
and are coated with slurry coating. The solution is
prepared with 40 g Kaolin + 1000 ml demineralised
water + sufficient amount of laboratory grade salt
(Nacl) to get a volume conductivity of 28 mS/cm i.e
2.8 S/m or an equivalent layer conductance of 8 US
or an SDD of 0.07 mg/cm2 . The flow of water is
adjusted to 100 ml/min from each nozzle. The
pressure of the compressed air is adjusted to 7
kglcn? . The connection diagram is shown in Figs.
1,2,3. The number of nozzles opened are 7. The
maximum length of nozzle column is 3.6 ni.
The string is placed in the top position as
shown in Fig 1. A supply voltage of 500 V is applied
at every five minutes and leakage current is
measured. Thus the test is conducted upto 90 min. A
graph is drawn between the time in minutes and per
unit leakage current. The graph is compared with the
standard graph in IEC 507.The test is repeated twice
for checking the repeatability.
1.2 Reference Test .
The cleaned specimen is coated with pollution
coating depending on the required salinity, by
dipping. Rain fog is sprayed on to the specimen. The
voltage applied depends on the profile,
contamination degree and overall creepage as
specified in IEC-507 standard. The test duration is
one hour. It is conducted for three times, out of
which three times the specimen -must withstand. If
one of them fails the test is conducted for fourth
time. If it passes, the specimen is deemed to have
passed the test otherwise, failed. The object of this
test is to confirm the specified withstand degree of
pollution at specified voltage.
2.0 Test Procedures 121
The test specimen is cleaned and dried. The
slurry coating is applied and dried. The number of
nozzles to be opened are chosen such that the wetting
action is uniform The length of nozzle columns is
chosen depending on .the length of the string of
insulators. Two standard disc insulators are taken for
the test. These insulators are placed at different
heights with respect to the lowest nozzle. of the
nozzle column. This setup is used to conduct the
layer conductance test. The test is performed for a
-132 kV system ( 9 disc Insulators ). For the reference
test, nine disc insulators are used, coated with the
suspension and number of nozzles opened were same
as in the case of layer conductance test. Alternate
nozzles are opened on both sides and also flowmeters
are adjusted to control the wetting rate.
Now the string is put in the middle position
( Fig.2 ) and the test is repeated.
Same procedure is repeated for the bottom position
also. (Fig.3 ).
Authorized licensed use limited to: Biblioteka Glowna i OINT. Downloaded on March 08,2010 at 03:17:10 EST from IEEE Xplore. Restrictions apply.
255208996.002.png
4.1 13.S25
3 times,out of which 3 must withstand . If the test
specimen passes two times and fails once, the test is
conducted for the 4" time. If it withstands it has
passed the test, otherwise it fails to withstand the
particular severity.
2.2.2 Precautions
2.1.1 Precautions
a) The slurry coating should be uniform on
the top and bottom surfaces of the insulator.
b). The insulator string is erected after
ensuring the flow of solution ,air pressure etc. are as
per standards.
c). The minimum clearances between any
part of the insulator and any earthed object other than
the structure which supports the insulator and the
columns of the nozzles, when used shall be not less
than 0.5 m / 100 kV of the test voltage and in any
case not less than 1.5 m.
Before conducting the next test, the
previously conducted test specimen must be earthed
before handling.
e). The supply must be adjusted continuously
up to the specified value to compensate for the
decrease in voltage due to scintillations.
9. The supply must be readily switched off
when there is a pollution flashover during the test to
protect the equipment. Overload tripping device can
be used for the protection of the equipment.
a. The slurry coating is such that it is more
uniform (as specified in IEC 507 standard) on the top
and bottom surfaces of the insulators.
b. The metal-parts i.e cap and pin a:: 1w-y
clean so that the contacts have very less resistance.
c.The discharge from all the nozzles must
be uniform.
d).
2.2 Reference Test
For the reference test, 9 IEEE standard disc
insulators ( shown in Fig.4 ) are used.
3.0 Results
Layer Conductance Test:
.. .
The insulators are coated-with the specified volume
conductivity i.e. 28 mS/cm. The total string
alongwith the dummy insulators, is hung in between
the nozzle columns. Number of nozzles, pressure of
compressed air, water conductivity etc. are same as
used in the layer conductance test. A voltage of 76
kV is applied , as per standard IEC 507, for IEEE
standard disc with an SDD of 0.07 mg/cm2 .
The wetting action of the Rain Fog test was
conducted on 2 nos. of IEEE standard disc insulators.
To startwith, the compressed air pressure is
maintained at 7 kg/cm2 and the discharge rate of tap
water varied and 3.6 m length of nozzle column
suitable for conducting pollution test on 220 kV
insulator was considered. It was found that for
discharge rates of 210 mumin, the wetting rate was
faster as compared to the standard wetting curve
given in IEC. Consequently, the discharge and
number of nozzles have been reduced. The result of
9 nos. of nozzles and discharge rate of 150 nillniin is
given . Here also the wetting rate is faster. The
discharge rate of tap water for nozzles is further
reduced.
It was found that, for an average water
discharge rate of 75 ml/min k 10 ml/min, the wetting
action of rain fog is comparable with that of standard
curve given in IEC. Number of tests have been
conducted to ensure the repeatability of the results.
It was found that the results are repeatable.
2.2.1 Test procedure
A test voltage of 76 kV is applied to the pin
of the lowest insulator string. The test arrangement is
shown in Fig 4. The voltage is applied for 1 hour to
check the withstand capability. This test is conducted
Authorized licensed use limited to: Biblioteka Glowna i OINT. Downloaded on March 08,2010 at 03:17:10 EST from IEEE Xplore. Restrictions apply.
--...
255208996.003.png
4.114.S25
The position of the two disc insulators is
also varied so as to verify the effect of the position of
the insulator string . It was found that the discharge
rate of nozzles i.e 75 mVmin t 10 mVmin and using
the alternative nozzles. i.e nozzles seperated by 1.2
m each, the standard wetting action curve is obtained
at difrerent string positions. The comparison of the
results ( with the string at different positions ) with
the standard curve is shown in Figure 5.
Number of nozzles to be used will be alternate
unlike in salt fog method i.e nozzles spaced at 1.2
m.
For the given discharge rate of 75 mYmin f 10
mVmin and position of the nozzles used
alternatively, the standard wetting action curve
could be obtained and the no. of tests conducted
to establish the same prove the repeatability.
The reference test conducted on 9 disc insulators
show that it withstood for a voltage of 76 kV for
a given SDD of 0.07 mg/cm2 as specified for
solid layer test.
The Rain fog test facility developed can at
present be used up a to system voltage of 132 kV.
The existing salt fog test nozzle column can be
used to conduct the test. In the case of the solid
layer test it is expensive to erect the tent, and
also for providing heaters to wet the pollution
layer. For higher system voltages the amount
required to be spent for steam fog test will be still
more. The test facility developed can be used to
conduct the rain fog test up to a system voltage of
220 kV.
Reference test:
The reference test was conducted on 9
standard disc insulators to validate the test procedure
developed. The insulator string withstood an SDD of
0.07 mgkm at a test voltage of 76 kV and at a
creepage distance of 20 dV
.
PER UNIT LAYER CONDUCTANCE
1.2
VS TIME
-4- TOP
+ Middle
+ Bottom
-8- standard I
Acknowledgements
The authors would like to thank the CPRI
authorities for permitting to publish this paper.
We also acknowledge the contributions of Mr.
A.Yellaiah, Miss G. Girija, A.Ramulu and Mr. N.
S. Parthasarathy in the form of discussion at
various stages of project.
-0.2
Test Time (min) 3
.-
Fig.5 The comparison of the results with the
standard wetting action curve .
References
4.0 Conclusion: -
[ 11 IEC 507,1991. Artificial Pollution Test
on high voltage insulators to be used on AC
system”.
[2] A.P.Sudheer, “Development of Rain
Fog Test Facility “, M.Tech Thesis, JNTU,
Kakinada, India. 1997.
In order to obtain the correct wetting action
of the rain fog, the discharge rate of the tap water,
number of nozzles and their position is varied, the
following conclusions are drawn from the results of
the tests conducted on insulator to establish the a
Rain fog test facility:
1. The average water discharge rate of 75 mYmin f
10 mVmin is found to be appropriate to obtain the
proper wetting action.
Authorized licensed use limited to: Biblioteka Glowna i OINT. Downloaded on March 08,2010 at 03:17:10 EST from IEEE Xplore. Restrictions apply.
255208996.004.png
Zgłoś jeśli naruszono regulamin