Version 1 and higher (firmware version V4.0 and higher)
for SIMATIC S7-400 / S7-400H
Status and fault LEDs
Mode selector
PROFIBUS interface
(9-pin D-sub female
connector)
43519721.007.png 43519721.008.png
Notes on the Product
Notes on the Product
Note
All notes in the product information bulletin , which is supplied with this product,
are valid and must be observed.
Compatibility with the Previous Version
Note
Make sure that you read the information regarding extended functionality and
restrictions in Chapter 6 of this manual!
B3 - 2
CP 443-5 Basic for PROFIBUS / Manual Part B3
Release 11/2002
C79000-G8976-C161-04
43519721.009.png 43519721.010.png 43519721.001.png
Contents
Contents - Part A
PROFIBUS CPs - General Information
. . . . . . . . . . . . . .
See General Part
Note
Please remember that Part A of the manual also belongs to the description of the
CP. Among other things, it contains explanations of the safety notices, references,
and general information that applies to all S7 CPs for PROFIBUS.
You can also download this general part from the Internet:
http://www4.ad.siemens.de/view/cs/de/8774037
Contents - Part B3
1
Properties / Services
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B3- 4
2
Requirements for Use
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B3- 7
2.1
Use with the Current CPU Types
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B3 - 7
2.2
Converting older Systems
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B3 - 8
3
Installation and Commissioning
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B3- 9
4
Displays and Mode Selector
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B3- 10
5
Performance Data
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B3- 12
5.1
Supported Transmission Rates
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B3 - 12
5.2
Data of S5-Compatible Communication (SEND/RECEIVE Interface)
on FDL Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B3 - 12
5.3
Data of FMS Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B3 - 13
5.4
Characteristics of S7 Communication
. . . . . . . . . . . . . . . . . . . . . . . . . . .
B3 - 14
5.5
Maximum Number of Connections in Total
. . . . . . . . . . . . . . . . . . . . . . .
B3 - 16
5.6
Time-of-day Synchronization
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B3 - 16
5.7
Use in Fault-Tolerant Systems
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B3 - 17
5.8
Other Characteristics
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B3 - 18
6
Compatibility with the Previous Product
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B3- 19
6.1
Extended Functionality Compared with Previous Product
. . . . . . . . . .
B3 - 19
6.2
Replacing Older Modules / Replacing Defective Modules
. . . . . . . . . .
B3 - 20
7
Technical Specifications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B3- 22
CP 443-5 Basic for PROFIBUS / Manual Part B3
Release 11/2002
C79000-G8976-C161-04
B3 - 3
43519721.002.png 43519721.003.png
Properties / Services
1
Properties / Services
Application
The CP 443-5 Basic communications processor is designed for use in a SIMATIC
S7-400 (standard) and S7-400H (fault-tolerant system) programmable controller. It
allows the S7-400 / S7-400H to be connected to a PROFIBUS fieldbus system.
Services
The current version of the CP 443-5 Basic supports the following communication
services in the standard and H systems:
PROFIBUS FMS (complying with EN 50170, FMS client and server function)
as FMS master for the following types of connection:
- MMAC: Master-master acyclic
- MSAC: Master-slave acyclic
- MSAC_SI: Master-slave acyclic with slave initiative
- MSCY: Master slave cyclic
- BRCT (broadcast): Sending to all FMS stations
S7 communication and PG/OP communication
- PG functions with upload / download of FM modules, configuration /
diagnostics and routing, user programs
Note on routing: Dynamic switchover to alternative paths (for example if
there is a problem on one of the possible transmission paths) is not
supported.
- Operator control and monitoring functions (HMI)
- Data exchange using communication function blocks on S7 connections
(fault-tolerant S7 connections also possible) 1 )
1)
Blocks for S7 communication (see also STEP 7 online help or
“System Software for S7-300/400 System and Standard Functions” manual) :
BSEND
SFB 12
BRCV
SFB 13
PUT
SFB 14
GET
SFB 15
USEND
SFB 8
URCV
SFB 9
START
SFB 19
STOP
SFB 20
RESUME
SFB 21
STATUS
SFB 22
USTATUS
SFB 23
CONTROL
SFC 62
B3 - 4
CP 443-5 Basic for PROFIBUS / Manual Part B3
Release 11/2002
C79000-G8976-C161-04
43519721.004.png
 
Properties / Services
S5-compatible communication (SEND/RECEIVE Interface) over FDL
connections of the following types:
- specified FDL connections
- free layer 2 connections
- broadcast
- multicast
Time-of-day synchronization over PROFIBUS
- The CP forwards time-of-day synchronization frames from the LAN to the
station (CPU = time slave) or from the station to the LAN (CPU= time
master) or this station is synchronized via a different LAN and the
time-of-day synchronization frame must be forwarded over PROFIBUS for
the synchronization of further stations.
- Time-of-day status value, standard/daylight saving time switchover,
synchronization status
The services of the CP 443-5 Basic module listed above can be used at the same
time.
Configuration
When configuring, you must use STEP 7 version V5.2 SP1 or higher; for FDL
connections and diagnostic functions, the NCM S7 for PROFIBUS optional
package supplied with STEP 7 must be installed.
If the functionality of the predecessor module is adequate for your purposes,
configuration and diagnostics are also possible with earlier STEP 7 versions.
It is possible to configure over the MPI or LAN/PROFIBUS.
System modifications are possible during operation (H system).
Note
For more detailed information on configuring PROFIBUS CP with STEP 7 /
NCM S7, refer to the manual NCM S7 for PROFIBUS and the online help of
STEP 7.
Programming - Using Blocks
For some communication services, there are “off-the-peg” blocks (FCs/FBs)
available that implement the interface in your STEP 7 user program. You will find a
detailed description of these blocks in the NCM S7 for PROFIBUS manuals.
CP 443-5 Basic for PROFIBUS / Manual Part B3