SIMATIC
FM 452
Getting Started
Edition 09/99
Commissioning Primer
153812357.002.png
Based on a concrete example, this primer guides you through five steps in which you install and start
up a functioning application with which you can create several distance cams on a rotary axis and
then try out and test the basic hardware and software functions of your FM 452. The references to the
manual will also help you to get a general overview of the information it contains.
Depending on your degree of experience, working through the sample will take between one and two
hours.
Requirements
The following requirements must be met:
You have installed STEP 7 (
.
V5.0) correctly on your programming device.
You have created a project for the S7-400 station.
The programming device is connected to the CPU.
You have an FM 452 module, the configuration package for the FM 452, an external
24 V DC power supply, and the necessary accessories such as the front connector and wiring.
Install the Configuration Package on the PG
The configuration package contains a parameter assignment tool for FM 452, the required functions
(FCs) and data structures (UDTs), and a sample program.
Insert the CD in your CD drive.
Start the software installation dialog in Windows by double-clicking the “Add/Remove Programs” icon
in the “Control Panel”.
Click the Install... button , select the Setup.exe file in the FMx52\Disk1 folder on the CD and follow the
instructions displayed by the installation program.
Install and Wire up the FM 452
Turn off the power supply and change the mode
selector on the CPU to STOP.
Rack
FM 452 front
connector
Hook the top of the FM 452 onto the rail in the
selected slot, swing it down and secure it with screws
(for more detailed information, refer to Chapter 3 of
the manual).
Refe-
rence
point
3
24 V DC
external
power sup-
ply
4
25
26
27
Wire up the front connector as shown in the picture
on the right (the full pinout of the front connector is
described in Chapter 4 of the manual).
Plug in the front connector on the FM 452 and secure
it with screws.
M
L+
35
36
37
47
48
Test: Turn on the power supply module and the external 24 V DC power supply.
The red EXTF LED on the FM 452 is lights up briefly and goes off again. The INTF LED
remains lit since you have not yet entered the FM 452 in the hardware configuration.
Set the Parameters for the FM 452
Open your project in the SIMATIC Manager.
Open the hardware object. The HW Config window is opened and displays the configuration table.
Select the FM 452 with the correct order number (MLFB) from the hardware catalog and drag it to the
slot you want to use.
If you double-click on this FM 452, you open the “Cam Controller – [FM 452 CAM (slot) (Setting
Parameters) -- project name\station name]” window of the parameter assignment user interface.
-2
You have an S7-400 station consisting of a power supply and a CPU.
153812357.003.png
Select the following settings in the parameter assignment dialogs (leave all other settings unchanged):
Axis
Rotary axis
End of the rotary axis:
360.0000 degrees
Simulation speed:
360.0000 degrees/min
Encoders
Monitoring
Deactivate wire break and missing pulses
Cam s:
No. Valid Track Type
Start
[deg]
End
[deg]
Time
[ms]
Lead time
[ms]
Activation
direction
Hardware
interrupt
0
0
Dist
0.0000
90.0000
0.0
Both
None
1
0
Dist
180.0000 270.0000
0.0
Both
None
2
1
Dist
0.0000
90.0000
2000.0
Both
None
3
1
Dist
180.0000 270.0000
2000.0
Both
None
4
2
Dist
130.0000 330.0000
0.0
Both
None
5
3
Dist
130.0000 330.0000
2000.0
Both
None
Save the settings in the parameter assignment user interface with File
"
Save and close the user
Exit .
Save your configuration in your project with Station
"
Save and Compile .
Transfer the configuration with the CPU in the STOP mode using PLC
"
Download. .. .
The data are then transferred directly to the CPU and the FM 452. The INTF LED on the FM 452 goes
off. From now on, as long as the configuration on the CPU remains battery backed, the data will
always be transferred from the CPU to the FM 452 whenever the CPU changes from STOP to RUN.
"
Commission , open the commissioning dialog
“Cam Controler - [FM 452 CAM (slot) Commision -- project name\station name]”.
In “Enable track signals”, select the track signals 0 to 3 and enable them by clicking the Apply button.
In “Other test functions”, select the “Function switch” and then the setting “Set reference point”, enter
0.000 degrees as the reference point, and click the Apply button. This synchronizes the axis; the
“Synchronized” box in the commissioning dialog is displayed in green.
In “Other test functions”, select the “Simulation on” option and click the Apply button.
Click the On button below “Enable test”.
Click the On button below “Cam controller”. As a reaction to this, the “Cam processing active” box and
the track signals 0 and 1 are displayed in green, since in this example, the cam start was set to 0 for
tracks 0 and 1.
Click the Dir_P button below “Simulation direction”.
The encoder signals are now simulated. You can monitor the actual value and the track signals
(green = at least one cam active; gray = no cam active). You can also follow the track signals at the
LEDs of outputs Q0 to Q3 of the FM 452.
"
Libraries .
Copy FC 0, FC 1 and UDT 1 from the Blocks folder of the FMx52LIB library to the “Blocks” folder of
your project.
Select the menu command Insert
"
Open...
"
Data Block and insert DB 1 in the “Blocks” folder of
your project and then select the menu command Insert
"
S7 Block
"
"
S7 Block
"
Organization Block and insert
OB100 .
Open DB 1 and create it with the assigned user–defined data type UDT 1. This creates the
channel DB.
Save DB 1 with File
"
Save and close the DB editor with File
"
Exi t .
-3
System of units: degrees (4 decimal places)
interface with File
Testing the FM 452
Start the parameter assignment user interface again by double-clicking the FM 452 in HW Config.
With Test
Linking into your User Program
Open the FMx52LIB library in the SIMATIC Manager with File
153812357.004.png
Properties.. . in the parameter
assignment user interface of the FM 452. Click the Mod Addr. .. button, select DB 1 and confirm with
OK .
Now open OB 1 and OB 100 in your project. Call FC1 in OB1 and FC0 in OB100 and supply the FCs
with parameters (see manual, Section 6.2 or 6.3):
OB1:
CALL FC1
DB_NO := 1
RET_VAL := FW0
"
OB100:
CALL FC0
DB_NO := 1
Save .
Select the blocks FC0, FC1, DB1, OB1 and OB100 in your project.
Download the your program to the CPU with PLC
"
Download .
Test: Using the “Monitor and Modify Variables” function, you can now, for example, monitor the cam
data, the cam tracks, and the actual value:
Create a symbol with the “CAM” for DB1.
Select the “Blocks” folder in your project. Using the menu command Insert
"
"
S7 Block
"
Variable Table , insert the variable table VAT and confirm with OK .
Open the variable table VAT1 and make the following entries in the “Symbol”, “Monitor Format”
and “Modify Value” columns:
Address
Symbol
Monitor
Format
Monitor
Value
Modify
Value
Meaning
DB1.DBW 16 CAM.TRACK_EN
HEX
FFFF
Enable track signals
DB1.DBD 98
CAM.REFPT
DEC
0
Reference point coordinate
DB1.DBX 36.3 CAM.REFPT_EN
BIN
1
Set reference point
DB1.DBX 15.4 CAM.CAM_EN
BIN
1
Cam controller on
DB1.DBX 34.1 CAM.SIM_ON
BIN
1
Simulation on
DB1.DBX 15.3 CAM.DIR_P
BIN
1
Simulation direction positive
DB1.DBD 26
CAM.ACT_POS
DEC
Current actual value
DB1.DBD 30
CAM.TRACK_OUT
BIN
Track signals
Save the variable table VAT1 with Table
"
Save .
Go online with PLC
"
Connect To
"
Configured CPU .
Switch to monitoring with Variable
"
Monitor.
Activate Modify Values , you make the modify values valid.
In the “Monitor Value” column, you can now observe the current actual value ( ACT_POS) and
the track signals ( TRACK_OUT ).
"
Diagnostics
Errors can occur due to incorrect operator input, incorrect wiring, or conflicting parameter settings.
How to deal with such errors and messages is described in Chapter 11 of the manual.
Example
The project zEn19_01_FMx52_Prog contains further samples that can you can use for further
practice or that you can adapt for your own particular application.
Siemens AG
Bereich Automatisierungs und Antriebstechnik
Geschäftsgebiet IndustrieAutomatisierungssysteme
Postfach 4848, D90327 Nürnberg
Siemens AG 1999
Subject to change
Siemens Aktiengesellschaft
C79000Z7076C457
Printed in the Fed. Rep. of Germany
-4
Now enter the module address in DB 1 as follows: Select File
Save both OB1 and OB100 with File
Change the CPU to RUN-P.
With Variable